Type SE XHHW Aluminum Cable (SER)
UL Type SE, Style R Aluminum Cable features UL Type XHHW aluminum conductors, rated 90°C for dry or wet locations and 600 V. It is suitable for above-ground service entrance cable, panel feeder, and branch circuit applications per NEC Article 338. Available in two, three, and four conductor configurations. The conductor is made of annealed compact stranded AA-8000 series Aluminum Conductor Material (ACM) with abrasion-, moisture-, and heat-resistant XLPE insulation. The cable includes a bare conductor, flame-retardant fiberglass-reinforced binder tape, and a sunlight-resistant, RoHS-compliant, flame-retardant gray PVC outer jacket.
- Applications
- Construction
- Conductor Identification
- Voltage Rating
- Temperature Ratings
- Min. Bending Radius
- Standards
- Listings and Certifications
- Packaging
These cables are manufactured and tested to meet or exceed the following standards:
- ASTM B800 — 8000 Series Aluminum Alloy Wire for Electrical Purposes—Annealed and Intermediate Tempers
- ASTM B801 — Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation
- UL 44 — Thermoset-Insulated Wires and Cables
- UL 854 — Service-Entrance Cables
- ICEA S-95-658 / NEMA WC70 — Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
- Federal Specification AA-59544
- Federal specification JC-30B
- Conductor: Annealed compact stranded AA-8000 series Aluminum Conductor Material (ACM).
- Insulation: Abrasion, moisture, and heat resistant color coded crosslinked polyethylene (XLPE), UL Type XHHW.
- Assembly: Solid bare wires are helically applied over a pair of parallel insulated conductors. A flame retardant fiberglass reinforced binder tape assembles the core in a flat configuration.
- Tape and Finish Covering: Sunlight resistant, RoHS compliant, flame retardant, gray polyvinyl chloride (PVC) material.
- 90°C Dry or Wet.
-
Overall Diameter Less than or Equal to 1.000 in
- Not Under Tension: 4x outer diameter
- Under Tension (During Pull): 6x outer diameter
Overall Diameter Greater than 1.000 in
- Not Under Tension: 5x outer diameter
- Under Tension (During Pull): 7.5x outer diameter
- 250 ft reels
- 500 ft reels
- 1000 ft reels
- Master reels
- Coils